APPLICATION: Suitable for energy transport and the transmission of signals and controls where a certain level
of mechanical protection (rodents-termites) is required. In the most risky environments in
the event of a fire, such as health facilities, entertainment venues and entertainment in general,
gyms and sports centers. Hotels, guest houses, motels, villages, tourist residences - hotels.
Schools of every order, grade and type. Exhibitors and / or retailers. Companies and offices.
INSTALLATION: For fixed indoor and outdoor installation even in wet enviroments. They can be installed on wall and metal structures, on platforms, pipes, conduits and similar systems. Cable for direct and indirect burial.
|
| FEATURES | DESCRIPTION | STANDARD |
| Conductors: |
Annealed red copper cl.5 |
CEI EN 60228 (Tab. 9) |
| Insulation: |
LSZH compound, G16 quality |
CEI EN 50363 |
| Cores colour: |
|
CEI UNEL 00722 - HD 308 |
| Inner sheath: |
LSZH compound |
CEI EN 50363 |
| Armour: |
Steel wire with steel tape wrapped helically |
|
| Outer sheath: |
LSZH compound, M16 quality |
CEI EN 50363 |
| Outer sheath colour: |
green RAL 6018 |
|
| Halogens free: |
(< 0,5 mg/g - 0,5%) |
CEI EN 50267-2-1/2 - IEC 60754-1/2 |
| Low toxic gases emission: |
(toxicity index < 2%) |
CEI 20-37/4-0 |
Rated voltage Uo/U: |
0,6/1 kV |
|
| Max. voltage: |
1,2 kV |
|
| Testing voltage: |
4 kV |
|
| Max working temperature: |
90 °C
|
|
| Short-circuit temperature: |
250 °C |
|
| Min. installation temperature: |
0 °C |
|
| Bending radius: |
Ø x 14 |
|
| Max standard twisting (2x cable): |
≥ 10 twists/meter |
|
| REGULATION (UE) 305/2011 |
| System AVCP : |
1+ |
EN 50575:2014 + A1:2016 |
| Classification : |
Cca-S1a,do,a1 |
UNI EN 13501-6 |
| Cca : |
Heat release and flame spread (FS ≤ 2m) |
EN 50399 |
| s1a : |
Smoke transmittance ≥ 80% (TSP ≤ 50 m2 and SPR ≤ 0.25 m2) |
EN 50399 + EN 61034-2 |
| d0 : |
No flaming droplets |
EN 50399 |
| a1 : |
Gas acidity (Conductivity <2.5 ms / mm and pH> 4.3) |
EN 50267-2-3 |
|
Flame propagation (H ≤ 425 mm) |
EN 60332-1-2 |
| Printing: |
BERICA CAVI S.P.A. ITALY FG16OFM16 0,6/1 kV Cca-S1a,do,a1 CE Year/Lot - Type - 00000 m |
|
|
|
TYPE N° x mm2 | MEDIUM Ø OUTER mm | MEDIUM WEIGHT kg/km | PRODUCT CODE |
| 2x1,5 | 12,0 | 286 | B22C02150 |
| 3G1,5 | 12,5 | 313 | B22C03150 |
| 4G1,5 | 13,4 | 350 | B22C04150 |
| 5G1,5 | 14,3 | 399 | B22C05150 |
| 7G1,5 | 15,2 | 462 | B22C07150 |
| 10G1,5 | 18,4 | 600 | B22C10150 |
| 12G1,5 | 19,2 | 681 | B22C12150 |
| 16G1,5 | 21,1 | 821 | B22C16150 |
| 19G1,5 | 22,1 | 905 | B22C19150 |
| 24G1,5 | 24,9 | 1097 | B22C24150 |
| 2x2,5 | 12,8 | 330 | B22C02250 |
| 3G2,5 | 13,4 | 371 | B22C03250 |
| 4G2,5 | 14,4 | 422 | B22C04250 |
| 5G2,5 | 15,4 | 478 | B22C05250 |
| 7G2,5 | 16,7 | 581 | B22C07250 |
| 10G2,5 | 20,2 | 775 | B22C10250 |
| 12G2,5 | 21,1 | 859 | B22C12250 |
| 16G2,5 | 23,4 | 1053 | B22C16250 |
| 24G2,5 | 27,4 | 1410 | B22C24250 |
| 2x4 | 14,2 | 409 | B22C02400 |
| 3G4 | 14,8 | 456 | B22C03400 |
| 4G4 | 16,1 | 544 | B22C04400 |
| 5G4 | 17,4 | 618 | B22C05400 |
| 2x6 | 15,7 | 499 | B22C02600 |
| 3G6 | 16,4 | 575 | B22C03600 |
| 4G6 | 17,7 | 666 | B22C04600 |
| 5G6 | 19,3 | 786 | B22C05600 |
| 2x10 | 17,8 | 661 | B22C021000 |
| 3G10 | 18,9 | 774 | B22C031000 |
| 4G10 | 20,7 | 934 | B22C041000 |
| 5G10 | 22,4 | 1090 | B22C051000 |
| 2x16 | 20,6 | 900 | B22C021600 |
| 3G16 | 21,7 | 1055 | B22C031600 |
| 4G16 | 23,8 | 1280 | B22C041600 |
| 2x25 | 24,2 | 1229 | B22C022500 |
| 3G25 | 25,6 | 1471 | B22C032500 |
| 4G25 | 28,1 | 1779 | B22C042500 |
|