PDF

FG16OAM16 0,6/1 kV

Power, control and signaling cables, with steel braid armour, fire retardant and halogens free

  1. Conductor
  2. Insulation
  3. Inner sheath
  4. Armour
  5. Outer sheath

Cca-S1a,do,a1

APPLICATION: Suitable for energy transport and the transmission of signals and controls where a certain level of mechanical protection (rodents-termites) is required.In the most risky environments in the event of a fire, such as health facilities, entertainment venues and entertainment in general, gyms and sports centers. Hotels, guest houses, motels, villages, tourist residences - hotels. Schools of every order, grade and type. Exhibitors and / or retailers. Companies and offices with more than 300 people present; Libraries and archives, museums, galleries, exhibitions and exhibitions. Buildings intended for civil use, with a fire height of more than 24m. (Average Risk)

INSTALLATION: For fixed indoor and outdoor installation even in wet enviroments. They can be installed on wall and metal structures, on platforms, pipes, conduits and similar systems. Cable for direct and indirect burial.

FEATURESDESCRIPTIONSTANDARD
Conductors: Annealed red copper cl.5 CEI EN 60228 (Tab. 9)
Insulation: LSZH compound, G16 quality CEI EN 50363
Cores colour: CEI UNEL 00722 - HD 308
Inner sheath: LSZH compound CEI EN 50363
Armour: Steel braid
Outer sheath: LSZH compound, M16 quality CEI EN 50363
Outer sheath colour: Green RAL 6018
Halogens free: (< 0,5 mg/g - 0,5%) CEI EN 50267-2-1/2 - IEC 60754-1/2
Low toxic gases emission: (toxicity index < 2%) CEI 20-37/4-0
Rated voltage Uo/U:: 0,6/1 kV
Max. voltage: 1,2 kV
Testing voltage: 4 kV
Max working temperature:

90 °C

Short-circuit temperature: 250 °C
Min. installation temperature: 0 °C
Bending radius: Ø x 14
TMax standard twisting (2x cable): ≥ 10 twists/meter
REGULATION (UE) 305/2011
System AVCP : 1+ EN 50575:2014 + A1:2016
Classification : Cca-S1a,do,a1 UNI EN 13501-6
Cca : Heat release and flame spread (FS ≤ 2m) EN 50399
s1a : Smoke transmittance ≥ 80% (TSP ≤ 50 m2 and SPR ≤ 0.25 m2) EN 50399 + EN 61034-2
d0 : No flaming droplets EN 50399
a1 : Gas acidity (Conductivity <2.5 ms / mm and pH> 4.3) EN 50267-2-3
Flame propagation (H ≤ 425 mm) EN 60332-1-2
Printing: BERICA CAVI S.P.A. ITALY FG16OAM16 0,6/1 kV Cca-S1a,do,a1 CE Year/Lot - Type - 00000 m

TYPE
N° x mm2
MEDIUM Ø OUTER
mm
MEDIUM WEIGHT
kg/km
PRODUCT CODE
2x1,510,9184B17C02150
3G1,511,4206B17C03150
4G1,512,1237B17C04150
5G1,513,2276B17C05150
7G1,514,1330B17C07150
10G1,517,2451B17C10150
12G1,518,0504B17C12150
16G1,520,0633B17C16150
19G1,521,2720B17C19150
24G1,523,8876B17C24150
2x2,511,8221B17C02250
3G2,512,3251B17C03250
4G2,513,3300B17C04250
5G2,514,4345B17C05250
7G2,515,7428B17C07250
10G2,519,1587B17C10250
12G2,520,1671B17C12250
16G2,522,3834B17C16250
24G2,526,51178B17C24250
2x413,1279B17C02400
3G413,7329B17C03400
4G414,9396B17C04400
5G416,4466B17C05400
2x614,6364B17C02600
3G6 15,2424B17C03600
4G6 16,6512B17C04600
5G6 18,3608B17C05600
2x10 16,7504B17C021000
3G10 17,8610B17C031000
4G10 19,6751B17C041000
5G10 21,4881B17C051000
2x16 19,7728B17C021600
3G16 20,8872B17C031600
4G16 22,71065B17C041600
2x2523,21014B17C022500
3G2524,51231B17C032500
4G25 27,11526B17C042500

Berica Cavi Spa reserves the right to edit all the information on the website without providing prior notice to customers and / or users