PDF

(N)HXH 0,6/1 kV (E30) (PH90/120)

Power, control and signalling cables, fire resistant, fire retardant, halogen free.

 

  1. Conductor
  2. Flame protection
  3. Insualtion
  4. Sheath

 

APPLICATION: Suitable for the transport of energy and the transmission of signals and controls for electrical equipment when you need maximum security against fire, such as emergency lighting and alarm systems, automatic fire detection, fire extinguishing equipment, automatic opening doors, ventilation systems and conditioning, emergency telephone systems.

 

INSTALLATION: For fixed indoor and outdoor installation in dry or wet environments. They can be installed on walls and metal structures, on platforms, pipes, conduits and similar systems. Cable for direct and indirect burial.



FEATURES DESCRIPTION STANDARDS
Conductors: annealed red copper CEI EN 60228 (Tab. 9)
Flame protection: mica-glass tape, thickness >0,10 mm  
Insulation: LSZH compound CEI EN 50363
Cores colour:   CEI UNEL 00722 - HD 308
Sheath: LSZH compound CEI EN 50363
Sheath colour: orange Ral 2004  
Fire retardant:   CEI EN 60332-3-24
Flame retardant:   CEI EN 60332-1-2
Halogen free: (< 0,5 mg/g - 0,5%) CEI EN 50267-2-1/2 - IEC 60754-1/2
Low toxic gases emission: (toxicity index < 2%) CEI 20-37/4-0
Low smoke emission: (trasmittance > 60%) CEI EN 61034-2
Fire resistant: duration 90 min. at temperature of 830 °C. (- 0 ÷ + 40 °C) CEI EN 50200 per Ø ≤ 20 mm
Fire resistant: duration 120 min. at temperature of 830 °C. (- 0 ÷ + 40 °C) CEI EN 50362 per Ø > 20 mm
Fire resistant: duration 180 min. at temperature of 750 °C (FE 180) IEC 60331-21 - VDE 472-814
Fire resistant: (E30) DIN VDE 4102-12
DC resistance: according to CEI EN 60228 (Tab. 9)
Current capacity:   CEI UNEL 35024/1 - CEI UNEL 35026
Rated voltage Uo/U: 0,6/1 kV  
Max voltage: 1,2 kV  
Testing voltage: 4 kV  
Max working temperature: 90 °C  
Short-circuit temperature: 250 °C  
Min. installation temperature: 0 °C  
Bending radius: Ø x 14  
Printing: BERICA CAVI S.P.A. ITALY (N)HXH FE180 / E30 IEC 60331-21 DIN VDE 4102-12 CE Year/Lot - Type 00000 m  
 
TYPE
N° x mm2
MEDIUM Ø OUTER
mm
MEDIUM WEIGHT
kg/km
PRODUCT CODE
1x1,5 7,0 68,0  
2x1,5 12,2 191,0  
3G1,5 12,8 217,0  
4G1,5 13,9 243,0  
5G1,5 15,1 298,0  
       
1x2,5 7,5 78,0  
2x2,5 13,0 224,0  
3G2,5 13,9 264,0  
4G2,5 14,9 310,0  
5G2,5 16,3 370,0  
       
1x4 8,0 96,0  
2x4 14,0 274,0  
3G4 15,0 327,0  
4G4 16,1 380,0  
5G4 17,6 477,0  
       
1x6 8,6 121,0  
2x6 15,2 342,0  
3G6 16,1

412,0

 
4G6 17,6 489,0  
5G6 19,3 612,0  
       
1x10 9,9 182,0  
2x10 17,8 496,0  
3G10 18,9 614,0  
4G10 20,7 756,0  
5G10 22,8 935,0  
       
1x16 11,0 246,0  
2x16 20,0 673,0  
3G16 21,2 819,0  
4G16 23,4 1021,0  
5G16 25,7 1267,0  
       
1x25 12,8 353,0  
2x25 23,6 900,0  
3G25 25,1 1206,0  
4G25 27,7 1481,0  
5G25 31,0 1868,0  
       
1x35 13,5 457,0  
1x50 15,5 650,0  
1x70 17,5 806,0  
1x95 20,1 1062,0  
1x120 22,6 1342,0  
1x150 24,9 1690,0  
1x185 27,7 1930,0  
1x240 29,1 2500,0  
       
7G1,5 14,2 315,0  
10G1,5 17,9 420,0  
12G1,5 18,9 492,0  
16G1,5 21,1 596,0  
19G1,5 22,3 693,0  
24G1,5 25,6 880,0  
36G1,5 30,5 1230,0  
48G1,5 35,1 1620,0  
       
7G2,5 15,8 412,0  
10G2,5 19,9 560,0  
12G2,5 21,1 650,0  
16G2,5 23,6 820,0  
19G2,5 25,0 930,0  
24G2,5 28,8 1180,0  
36G2,5 34,2 1810,0  
48G2,5 39,5 2450,0

 

Berica Cavi S.p.A. reserves the right to change all information on the website without giving prior notice to customers and / or users