FG7OH2R+T+ST 0,6/1 kV
Cables for electric motors controlled by inverter, red copper braid shield, with grounding conductor and screened pair for thermal probe outside from shield, fire retardant and low halogens emission.
|
 |
- Conductor
- Insulation
- Assembling
- Shiled
- Assembling
- Pair for thermal probe
- Sheath
|
|
APPLICATION: Suitable for the transport of energy and in particular for the power supply of electric motors controlled by inverter. The ground conductor external to the shield and the increased coverage of the shield serve to reduce the transmission of electromagnetic noise generated by the motor control.
INSTALLATION: For fixed indoor installation in industrial environments. They can be installed on wall and metal structures, on platforms, pipes, conduits and similar systems. Cable for direct and indirect burial.
|
| FEATURES |
DESCRIPTION |
STANDARDS |
| Conductors: |
annealed red copper cl.5 |
CEI EN 60228 (Tab. 9) |
| Insulation: |
LSZH compound, G7 quality |
CEI EN 50363 |
| Cores colour: |
black numbered 1-2-3 |
CEI UNEL 00722 - HD 308 |
| Assembling: |
Pet tape |
|
| Shield: |
braid of annealed red copper, covering >80% |
|
|
PAIR FOR THERMAL PROBE
|
| Conductors: |
annealed red copper sect. 1 mm² |
CEI EN 60228 (Tab. 9) |
| Insulation: |
LSZH compound, G7 quality |
CEI EN 50363 |
| Cores colour: |
black numbered 4-5 |
CEI UNEL 00722 - HD 308 |
| Assembling: |
Pet tape |
|
| Drain wire: |
annealed tinned copper, comp. 7x0,30 mm |
|
| Screen: |
Al/Pet tape |
|
| Assembling: |
Pet tape |
|
| |
| Sheath: |
PVC, TM2 quality |
CEI EN 50363 |
| Sheath colour: |
grey RAL 7035 |
|
| Fire retardant: |
|
CEI 20-22/II |
| Flame retardant: |
|
CEI EN 60332-1-2 |
| Low halogens emission: |
(< 22%) |
CEI EN 50267-2-1 - IEC 60754-1 |
| Oil resistant: |
|
CEI 20-34/0-1 |
| DC resistance: |
according to |
CEI EN 60228 (Tab. 9) |
| Current capacity: |
|
CEI UNEL 35024/1 - CEI UNEL 35026 |
| Rated voltage Uo/U: |
0,6/1 kV |
|
| Max. voltage: |
1,2 kV |
|
| Testing voltage: |
4 kV |
|
| Max working temperature: |
90 °C |
|
| Short-circuit temperature: |
250 °C |
|
| Min. installation temperature: |
0 °C |
|
| Bending radius: |
Ø x 15 |
|
| Printing: |
BERICA CAVI S.P.A. ITALY FG7XOH2 Type T+FG7XH Type 0,6/1 kV O.R. CEI 20-22 II CE Year/Lot |
|
|
|
TYPE N° x mm2 |
MEDIUM Ø OUTER mm |
MEDIUM WEIGHT kg/km |
PRODUCT CODE |
| 3x1,5 + 1G1,5 + 2x1 |
11,7 |
219,0 |
B5503150 |
| 3x2,5 + 1G2,5 + 2x1 |
13,2 |
313,0 |
B5503250 |
| 3x4 + 1G4 + 2x1 |
15,2 |
448,0 |
B5503400 |
| 3x6 + 1G6 + 2x1 |
17,2 |
591,0 |
B5503600 |
| 3x10 + 1G10 + 2x1 |
20,5 |
873,0 |
B55031000 |
| 3x16 + 1G16 + 2x1 |
23,4 |
1478,0 |
B55031600 |
| 3x25 + 1G25 +2x1 |
29,4 |
2010,0 |
B55032500 |
|
Berica Cavi Spa reserves the right to edit all the information on the website without providing prior notice to customers and / or users