PDF

SOLAR CABLE 2x 0,6/1 kV

Cables for applications in photovoltaic systems, with elastomeric insulation and sheath, flame retardant, halogen-free and UV resistant.

  1. Conductor
  2. Insulation
  3. Sheath

APPLICATION: Suitable for the interconnection of the components of PV systems are characterized by: optimum mechanical properties in a range of operating temperature - 40 to + 90 ° C, high abrasion resistance, tear, UV, ozone , water, flame propagation, low smoke, halogen-free, weather resistance that allows a period equal to the life of the PV system.

INSTALLATION: For fixed indoor and outdoor installation, without protection , or inside pipe surface mounted or embedded, or similar closed systems. Possibility of indirect or direct burial.



FEATURES DESCRIPTION STANDARDS
Conductors: annealed tinned copper cl.5 CEI EN 60228 (Tab. 9)
Insulation: crosslinked non-toxic elastomer
Colour cores: red and black
Sheath: crosslinked non-toxic elastomer
Sheath colour: black RAL 9005
Flame retardant: CEI EN 60332-1-2
Halogen free: (< 0,5 mg/g - 0,5%) CEI EN 50267-2-1/2 - IEC 60754-1/2
Low toxic gases emission: (toxicity index < 2%) CEI 20-37/4-0
Low smoke emission: (trasmittance > 60%) CEI EN 61034-2
UV resistant: HD 605
Ozone resistant: CEI EN 50396
Long-term behavior: (20000 h at 120 °C) CEI EN 60216
Expected life: 25 years
DC resistance: according to CEI EN 60228 (Tab. 9)
Current capacity: CEI 20-21 - IEC 60287
Rated voltage Uo/U: 0,6/1 kVac 0,9/1,5 kVdc
Max voltage: 1,2 kVac 1,8 kVdc
Testing voltage: 6,5 kac 15 kVdc
Max working temperature: 90 °C
Min working temperature: -40 °C
Short-circuit temperature: 250 °C
Min. installation temperature: -25 °C
Bending radius: Ø x 6
Printing: BERICA CAVI S.P.A. ITALY SOLAR CABLE Type Year/Lot PV1-F 1500 Vdc IEC 60332-1-2 CE 00000 m

TYPE
N° x mm2
MEDIUM Ø OUTER
mm
MEDIUM WEIGHT
kg/km
PRODUCT CODE
2x2,5 NERO 5,20x10,60 104 B8802250N
2x4 NERO 5,80x12,00 132 B8802400N
2x6 NERO 6,60x13,60 178 B8802600N
2x10 NERO 8,00x16,40 313 B88021000N
2x16 NERO 9,30x18,80 420 B88021600N

Berica Cavi Spa reserves the right to edit all the information on the website without providing prior notice to customers and / or users