PDF

UTP 4x2x22 AWG Cat.5E FR PH120

Data transmission cables, fire resistant, fire retardant and halogen-free

 

  1. Conductor
  2. Insulation
  3. Flame protection
  4. Sheath

 

B2ca-s1a,d1,a1

 

APPLICATION: Used for high-frequency data transmission, when there is a need to guarantee signal transmission even in the presence of fire (video surveillance systems, interconnections of central units for voice evacuation systems and fire detection systems). In environments at greatest risk in case of fire. Places characterized by high density occupation and difficult condition of evacuation such as terminals, railway stations, maritime stations, subways, road and railway tunnels (High risk).

INSTALLATION: For fixed installation indoors and outdoors (protected from UV rays), on metal structures, trays, pipes and similar systems. Burried installation is not allowed. They can be installed in the same conduit with circuits of electrical systems with rated voltage to earth up to 400 V, typically 230 / 400 V power systems.

 

FEATURES DESCRIPTION STANDARDS
Conductors: annealed red copper 0,63 mm (22AWG)  
Insulation 1: LSZH PP thermoplastic compound  
Insulation 2: LSZH silicone rubber  
Cores colour: white/blue - white/orange - white/green - white/brown  
Flame protection: glass-fibre tape  
Sheath: LSZH special thermoplastic compound  
Sheath colour: red RAL 3000  
Fire resistant: duratation 120 min. at 830 °C.(- 0 ÷ + 40 °C) PH120 CEI EN 50200
Fire resistant: duratation 180 min. at 750 °C FE180 IEC 60331-21 - VDE 472-814
DC resistance: < 190 Ω/km (loop)  
Impedance: 100 ± 5Ω a 100 MHz  
Cond-cond capacitance: of the order of 50 nF/km (1 kHz)  
Inductance: of the order of 0,75 mH/km (1 kHz)  
Testing voltage: 700 Vac x 1 min.  
Max working temperature: 70 °C  
Min. installation temperature: 0 °C  
Bending radius: Ø x 8  
REGULATION (UE) 305/2011
System AVCP : 1+ EN 50575:2014 + A1:2016
Classification : B2ca-s1a,d1,a1 UNI EN 13501-6
B2ca : Heat release and flame spread (FS ≤ 1.5m) EN 50399
s1a : Smoke transmittance ≥ 80% (TSP ≤ 50 m2 and SPR ≤ 0.25 m2 / s) EN 50399 + EN 61034-2
d1 : No flaming droplets/particles persisting longer than 10 s EN 50399
a1 : Gas acidity (Conductivity 4.3)
Flame propagation (H ≤ 425 mm)
EN 50267-2-3
EN 60332-1-2
Printing: BERICA CAVI S.P.A. ITALY UTP 4x2x22 AWG Cat.5E FR PH120 Uo=400 V 100
OHM B2ca-s1a,d1,a1 CE Year/Lot 00000 m
 

 

TYPE MEDIUM Ø OUTER
mm
MEDIUM WEIGHT
kg/km
PRODUCT CODE
UTP 4x2x22AWG 9,7 105 B76B04CA22FR

 

Berica Cavi Spa reserves the right to edit all the information on the website without providing prior notice to customers and / or users