
S/FTP 4x2x22 AWG Cat.5E FR PH120
Data transmission cables, Al/Pet tape and tinned copper braid screened, fire resistant, fire retardant and halogen-free
|
 |
- Conductor
- Insulation
- Flame protection
- Drain wire
- Shield
- Sheath
|

B2ca-s1a,d1,a1
|
|
APPLICATION: Used for high-frequency data transmission, when there is a need to guarantee signal transmission even in the presence of fire (video surveillance systems, interconnections of central units for voice evacuation systems and fire detection systems). In environments at greatest risk in case of fire. Places characterized by high density occupation and difficult conditions of evacuation such as terminals, railway stations, maritime stations, subways, road and railway tunnels (High risk).
INSTALLATION: For fixed installation indoors and outdoors (protected from UV rays), on metal structures, trays, pipes and similar systems. Burried installation is not allowed. They can be installed in the same conduit with circuits of electrical systems with rated voltage to earth up to 400 V, typically 230 / 400 V power systems.
|
| FEATURES |
DESCRIPTION |
STANDARDS |
| Conductors: |
annealed red copper 0,63 mm (22AWG) |
|
| Insulation 1: |
LSZH PP thermoplastic compound |
|
| Insulation 2: |
LSZH silicone rubber |
|
| Cores colour: |
withe/blue - white/orange - withe/green - white/brown |
|
| Flame protection: |
glass-fibre tape |
|
| Drain wire: |
annealed tinned copper 7x0,30 mm |
|
| Shield: |
Al/Pet tape |
|
| Shield: |
braid of annealed tinned copper |
|
| Sheath: |
LSZH special thermoplastic compound |
|
| Sheath colour: |
red RAL 3000 |
|
| Fire resistant: |
duration 120 min. at 830 °C. (- 0 ÷ + 40 °C) PH120 |
CEI EN 50200 |
| Fire resistant: |
duration 180 min. at 750 °C FE180 |
IEC 60331-21 - VDE 472-814 |
| DC resistance: |
< 120 Ω/km (loop) |
CEI EN 50288-2-1 |
| Impedance: |
100 ± 5Ω a 100 MHz |
|
| Cond-cond capacitance: |
of the order of 60 nF/km (1kHz) |
|
| Cond-shield capacitance: |
of the order of 85 nF/km (1kHz) |
|
| Inductance: |
of the order of 0,75 mH/km (1 kHz) |
|
| Testing voltage: |
700 Vac x 1 min. |
|
| Max working temperature: |
70 °C |
|
| Min. installation temperature: |
0 °C |
|
| Bending radius: |
Ø x 8 |
|
| REGULATION (UE) 305/2011 |
| System AVCP : |
1+ |
EN 50575:2014 + A1:2016 |
| Classification : |
B2ca-s1a,d1,a1 |
UNI EN 13501-6 |
| B2ca : |
Heat release and flame spread (FS ≤ 1.5m) |
EN 50399 |
| s1a : |
Smoke transmittance ≥ 80% (TSP ≤ 50 m2 and SPR ≤ 0.25 m2 / s) |
EN 50399 + EN 61034-2 |
| d1 : |
No flaming droplets/particles persisting longer than 10 s |
EN 50399 |
| a1 : |
Gas acidity (Conductivity 4.3) Flame propagation (H ≤ 425 mm) |
EN 50267-2-3 EN 60332-1-2 |
| Printing: |
BERICA CAVI S.P.A. ITALY S/FTP 4x2x22 AWG Cat.5E FR PH120 Uo= 400 V 100 OHM B2ca-s1a,d1,a1 CE Year/lot - 00000m |
|
|
|
| TYPE |
MEDIUM Ø OUTER mm |
MEDIUM WEIGHT kg/km |
PRODUCT CODE |
| S/FTP 4x2x22AWG |
10,2 |
108 |
B75B04CA22FR |
|
Berica Cavi Spa reserves the right to edit all the information on the website without providing prior notice to customers and / or users